Place of use
This type of cables is suıtable to use in machınary production, power stations, energy projects, conditioning-ventilation and other electrical systems, in dry and humid envıronments, especially in industrial environmental conditıons; with measuring, monitoring and controlling purposes. Halogen free cables have flame retardant properties and low smoke density.
Inner Conductor | Electrolytic Stranded Annealed Copper Wire, Class 2 |
Insulation | HFFR Compound EN 50290-2-26, |
Stranding | Cores Twisted in Layers |
Inner Sheath | HFFR Compound EN 50290-2-27, RAL 7001 Grey |
Screen | Tinned Copper Wire Braiding |
Outer Sheath | HFFR Compound EN 50290-2-27, RAL 7001 Grey |
Product Code | Dimension and Weights | Electrical Properties | |||||||||
Nominal Cross Section | Overall Diemeter ( ~ ) |
Net Weight ( ~ ) |
Standart Lenght | Max. Dc Conductor Resistance at 20◦ C | Current Carrying Capacity | ||||||
In Ground at 20° C | On Air at 30° C |
CONDUCTOR RESISTANCE | INSULATION RESISTANCE | CURRENT CARRYING CAPACITY | OPERATING VOLTAGE | TEST VOLTAGE | BENDING RADIUS | TEMPERATURE RANGE | ||
mm² 0,5 0,75 1,0 1,5 2,5 | Ω/km 39 26 19,5 13,3 7,98 | MΩxKm 20 MΩ.km | mm² 0,5 0,75 1,0 1,5 2,5 | A 6,0 13 16 20 25 | 300 / 500 V | 2000 V | 7,5XD | -30ºC+70ºC |
FLAME RETARDANT TEST | SMOKE DENSITY TEST | TEST ON CORROSIVENESS OF COMBUSTION GASES | HALOGEN FREE TEST | FLAME |
IEC 60332-1-2 VDE 0482-332-1-2 EN 60332-1-2 | IEC 61034-2 VDE 0482-1034-2 EN 61034-2 | IEC 60754-2 VDE 0482-267-2-3 EN 50267-2-3 | IEC 60754-1 VDE 0482-267-2-1 EN 50267-2-1 | IEC 60332-3-24 VDE 0482-332-3-24 EN 60332-2-24 |